Stainless Steel Photoelectric Level Sensor for Water/Liquid, PNP/ NPN

SKU: SUCH-LS-IR2102D
$129.99
● Stainless steel material with an infrared photoelectric measuring principle ● 1/4 NPT thread type, output signal NPN or PNP ● Maximum current consumption less than 15mA ● Suitable for pure, impure, and adhesive liquids level measurement
*
🚚 Free shipping
🕒 Delivery date: 6-12 days
🔁 30-day Returns
Overview

SUCH stainless steel photoelectric liquid level sensor uses infrared detection with strong resistance to sunlight interference and features a 1/4 NPT threaded structure for easy installation. This level switch supports NPN or PNP signal output with direct relay driving and operates with a maximum current consumption of less than 15mA, ensuring low power usage and fast response. Designed for pure, impure, and adhesive liquids, it integrates multiple protection functions and provides low-level warning and overflow prevention for safe system operation.

Dimension (Unit: mm)

Stainless steel photoelectric liquid level sensor dimension

3 Wire Signal Output and Circuit Diagram

Photoelectric liquid level sensor signal output and circuit diagram

Mounting Method

Photoelectric liquid level sensor mounting method

Use

Photoelectric liquid level sensor use

Specs
Structure Metallic structure
Type Strong acid and strong alkaline types
Material Stainless steel + glass
Signal Output NPN/ PNP
Contact Form NO/ NC
Action Mode 3 wire: Not switchable
Tread Type 1/4 NPT
Detected Object Water/ Neutral solution/ Non-viscous acid-alkaline solution
Detection Accuracy Less than plus or minus 1mm
Voltage DC5-24V (including voltage fluctuation 10%)
Max Current Consumption <15mA
Load Current below 100mA
Response Time 1ms, 0.25ms
Electrical Life More than 100,000 times (opening and closing frequency: 1800 times/hour)
Environmental Illumination Incandescent Lamp: 5000lx or less. Sunlight: 80,000lx or less
Environment Temperature ON: -30~+100℃ OFF: -40~+120℃ (with no icing and frosting)
Insulation Resistance above 20mΩ (500VDC)
Protection Level IP62
Connection Method Lead-out type (wire length 30cm)
Lead color definition Red VDC; Blue GND; Yellow out
Mass (Sensor Only) about 40g
Accessories Sealing ring, nut
Application
Photoelectric liquid level sensor for electrical industry

Electrical Industry

Photoelectric liquid level sensor for sewage treatment

Sewage Treatment

Photoelectric liquid level sensor for water purification

Water Purification

FAQ

Generally, they are unaffected by foam, bubbles, and steam because the significant difference in light refractive index prevents false triggering. However, if the foam is particularly thick and tightly wraps around the probe, it may cause false readings. High-temperature steam may also cause condensation to adhere to the probe, requiring anti-condensation treatment.

They can usually be installed in any direction, but vertical installation is recommended to reduce bubble adhesion. During installation, avoid placing the probe tip directly against the container wall or allowing excessive fluid flow velocity, as this can affect stability. If used in pipelines or small spaces, ensure sufficient contact between the probe tip and the liquid.

Photoelectric level sensors primarily rely on optical principles and are not sensitive to electromagnetic interference. No additional shielding is required under normal conditions. However, if installed near strong electromagnetic equipment, such as high-power frequency converters or welding machines, it is recommended to use shielded cables and proper wiring to improve stability.

0.0 0